Dorlen WM Series 2100 Remote Monitored System

Showing 1 - 4 of 4 items

The Series 2100 is an early warning leak detection system utilizing the latest line of Dorlen Products remote monitors and compatible OAX-2100 Oil Alert detectors. All Series 2100 Monitors Monitor and Power the connected OAX-2100 Oil Alerts. The easily installed system is made up of only 3 separate components, 1 Monitor (2 models available) , up to 12 Oil Alert detectors, and Dorlen type "F" interconnect cable. When one or more Oil Alert detects liquid leakage it will activate its internal audible alarm and signal the monitor. The monitor will then activate providing an audible alarm, red flashing lamp, LED indication of activated Oil Alert(s) and transfer a dual set of isolated relay contacts. The Oil Alerts may be located up to 2500 feet from the monitor.

Features

  • Monitors will monitor, power and TEST the connected Oil Alerts (Oil Alert Model OAX-2100).
  • WM-6(T) panel can monitor, power and test up to Qty. 6: OAX-2100 Detectors. WM-12(T) up to Qty.12 detectors.
  • Upon Oil Alert activation, monitors sound audible alarm, flashing red Lamp and LED indication of which Oil Alert has activated.
  • Monitors are equipped with automatic internal battery back-up in case of line power failure, system will remain monitoring for up to 2 days without AC power... Battery self recharges upon AC return.
  • Monitors are equipped with 2- SPDT isolated relay contacts which will transfer upon any Oil Alert activation for customer use in signaling existing security panels or other equipment. (Relays rated at 1 amp,28VDC).
  • Extremely simple installation...Normally carried out by company maintenance personnel with instructions furnished. ALL hardware included.
  • Ultra-reliable performance; All Monitors come with a 5 year Warranty...prices shown on attached price list.
  • Everthing needed to make your system functional and easy to install.

Specifications

Monitor Input Voltage/Current
115VAC 10%, 60Hz, .2Amp max
Monitor Output Voltage
9VDC (To detectors)
Monitor Audible Alarm
85db at 3 feet
Input
UL listed input transformer, Terminal strip hard wired
Dimensions / Wt. 6 & 12 channel
10"Wx5"Dx12"H / 20lbs TYPE F Cable

Applications

  • "Machining Centers
  • Hydraulic Equipment
  • Stand-by Equipment Monitoring
  • Coolant Oil Piping
  • Solvent Storage Locations
  • Elevator Pits
  • Oil Storage Locations
  • Hydraulic Piping
  • Remote Site Monitoring
  • Unattended / Obscured Areas"